FC322, P18KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
36
480
0.396
1.210
2.444
100
480
0.844
1.230
1.165
150
480
0.696
1.160
1.333
FC322, P22KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
36
480
0.312
2.846
100
480
0.556
1.250
1.798
150
480
0.608
1.230
1.618
FC322, P30KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
15
480
0.288
3.083
100
480
0.492
1.230
2.000
150
480
0.468
1.190
2.034
FC322, P37KT4
Cable
length [m]
Mains
voltage
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
480
0.368
1.270
2.853
50
480
0.536
1.260
1.978
100
480
0.680
1.240
1.426
150
480
0.712
1.200
1.334
FC322, P45KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
480
0.368
1.270
2.853
50
480
0.536
1.260
1.978
100
480
0.680
1.240
1.426
150
480
0.712
1.200
1.334
FC322, P55KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
15
480
0.256
1.230
3.847
50
480
0.328
1.200
2.957
100
480
0.456
1.200
2.127
150
480
0.960
1.150
1.052
FC322, P75KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
480
0.371
1.170
2.523
3 VLT Automation VT Drive Selection
Automation VT Drive FC322 Design Guide
70
MG.20.X1.22 - VLT
®
is a registered Danfoss trademark
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx