5.3 Electrical Installation
5.3.1 Cables General
NB!
Cables General
Always comply with national and local regulations on cable cross-sections.
Details of terminal tightening torques.
Power (kW)
Torque (Nm)
Enclosure
200-240 V
380-480 V
525-690 V
Mains
Motor
DC connec-
tion
Brake
Earth
Relay
A2
0.25 - 3.0
0.37 - 4.0
1.8
1.8
1.8
1.8
3
0.6
A3
3.7
5.5 - 7.5
0.75 - 7.5
1.8
1.8
1.8
1.8
3
0.6
A5
0.25 - 3.7
0.37 - 7.5
1.1 - 7.5
1.8
1.8
1.8
1.8
3
0.6
B1
5.5 -11
11 - 18
-
1.8
1.8
1.5
1.5
3
0.6
B2
- 15
22
30
11 -
30
2.5
4.5
2.5
4.5
3.7
3.7
2.5
4.5
3
3
0.6
0.6
B3
5.5 -
7.5
11 -
15
-
-
1.8
1.8
1.8
1.8
2 -
3
0.5 -
0.6
B4
11 -
15
18.5 -
30
-
-
4.5
4.5
4.5
4.5
2 -
3
0.5 -
0.6
C1
18.5 - 30
37 - 55
-
10
10
10
10
3
0.6
C2
37 - 45
75
90
30 -
90
14
24
14
24
14
14
14
14
3
3
0.6
0.6
C3
18.5 -
22
37 -
45
-
-
10
10
10
10
2 -
3
0.5 -
0.6
C4*
30
37
55
75
-
-
14
24
14
24
14
24
14
24
2 -
3
0.5 -
0.6
D1/D3
-
110
132
110
132
19
19
19
19
9.6
9.6
9.6
9.6
19
0.6
D2/D4
-
160-250
160-315
19
19
9.6
9.6
19
0.6
E1/E2
-
315-450
355-560
19
19
9.6
9.6
19
0.6
Enclosure
200-240 V
380-480 V
525-690 V
Mains
Motor
DC Con-
nection
Brake
Regen
Relay
F1/F2/F3/F4
-
500-1000
710-1200
19
19
9.6
9.5
19
0.6
Table 5.3: Tightening of terminals.
* For C4, tigtening torque depends on cable dimensions used - 35-95 mm
2
or 120-150 mm
2
.
5.3.2 Removal of Knockouts for Extra Cables
1.
Remove cable entry from the frequency converter (Avoiding foreign parts falling into the frequency converter when removing knockouts)
2.
Cable entry has to be supported around the knockout you intend to remove.
3.
The knockout can now be removed with a strong mandrel and a hammer.
4.
Remove burrs from the hole.
5 How to Install
Automation VT Drive FC322 Design Guide
140
MG.20.X1.22 - VLT
®
is a registered Danfoss trademark
5
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx