
Illustration 2.1: The graph is showing fan curves (A, B and
C) for reduced fan volumes.
Illustration 2.2: When using a frequency converter to reduce
fan capacity to 60% - more than 50% energy savings may
be obtained in typical applications.
2.7.3 Example of Energy Savings
As can be seen from the figure (the laws of proportionality), the flow is controlled by changing the RPM. By reducing the speed only 20% from the rated
speed, the flow is also reduced by 20%. This is because the flow is directly proportional to the RPM. The consumption of electricity, however, is reduced
by 50%.
If the system in question only needs to be able to supply a flow that corresponds to 100% a few days in a year, while the average is below 80% of the
rated flow for the remainder of the year, the amount of energy saved is even more than 50%.
The
laws of proportionality
The figure below describes the dependence of flow, pressure and power consumption on RPM.
Q = Flow
P = Power
Q
1
= Rated flow
P
1
= Rated power
Q
2
= Reduced flow
P
2
= Reduced power
H = Pressure
n = Speed regulation
H
1
= Rated pressure
n
1
= Rated speed
H
2
= Reduced pressure
n
2
= Reduced speed
2 Introduction to VLT Automation VT Drive
Automation VT Drive FC322 Design Guide
20
MG.20.X1.22 - VLT
®
is a registered Danfoss trademark
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx