FC322, P90KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
480
0.371
1.170
2.523
High Power Range:
FC322, P110 - P250, T4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
400
0.34
1.040
2.447
FC322, P315 - P1M0, T4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
500
0.71
1.165
1.389
30
400
0.61
0.942
1.233
FC322, P110 - P400, T7
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
690
0.38
1.513
3.304
30
575
0.23
1.313
2.750
30
690
1)
1.72
1.329
0.640
1) With Danfoss dU/dt filter.
FC322, P450 - P1M2, T7
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
690
0.57
1.611
2.261
30
575
0.25
2.510
30
690
1)
1.13
1.629
1.150
1) With Danfoss dU/dt filter.