Bit 13/14, Selection of set-up:
Use bits 13 and 14 to choose from the four menu set-ups according to
the shown table: .
Set-up
Bit 14
Bit 13
1
0
0
2
0
1
3
1
0
4
1
1
The function is only possible when
Multi Set-Ups is selected in
par. 0-10
Active Set-up.
NB!
Make a selection in par. 8-55
Set-up Select to define
how Bit 13/14 gates with the corresponding function
on the digital inputs.
Bit 15 Reverse:
Bit 15 = ’0’: No reversing. Bit 15 = ’1’: Reversing. In the default setting, reversing is set to digital in par. 8-54
Reversing Select. Bit 15 causes reversing
only when Ser. communication, Logic or or Logic and is selected.
7.11.2 Status Word According to FC Profile (STW) (par. 8-10
Control Profile = FC profile)
Bit
Bit = 0
Bit = 1
00
Control not ready
Control ready
01
Drive not ready
Drive ready
02
Coasting
Enable
03
No error
Trip
04
No error
Error (no trip)
05
Reserved
-
06
No error
Triplock
07
No warning
Warning
08
Speed
≠
reference
Speed = reference
09
Local operation
Bus control
10
Out of frequency limit
Frequency limit OK
11
No operation
In operation
12
Drive OK
Stopped, auto start
13
Voltage OK
Voltage exceeded
14
Torque OK
Torque exceeded
15
Timer OK
Timer exceeded
Explanation of the Status Bits
Bit 00, Control not ready/ready:
Bit 00 = ’0’: The frequency converter trips. Bit 00 = ’1’: The frequency converter controls are ready but the power component does not necessarily receive
any power supply (in case of external 24 V supply to controls).
Bit 01, Drive ready: