3.21 Parameters: 35-** Sensor Input Option
3.21.1 35-0* Temp. Input Mode (MCB 114)
35-00 Term. X48/4 Temp. Unit
Select the unit to be used with temperature input X48/4 settings
and readouts:
Option:
Function:
[60]
*
°C
[160]
°F
35-01 Term. X48/4 Input Type
View the temperature sensor type detected at input X48/4:
Option:
Function:
[0]
*
Not Connected
[1]
PT100 2-wire
[3]
PT1000 2-wire
[5]
PT100 3-wire
[7]
PT1000 3-wire
35-02 Term. X48/7 Temp. Unit
Select the unit to be used with temperature input X48/7 settings
and readouts:
Option:
Function:
[60]
*
°C
[160]
°F
35-03 Term. X48/7 Input Type
View the temperature sensor type detected at input X48/7:
Option:
Function:
[0]
*
Not Connected
[1]
PT100 2-wire
[3]
PT1000 2-wire
[5]
PT100 3-wire
[7]
PT1000 3-wire
35-04 Term. X48/10 Temp. Unit
Select the unit to be used with temperature input X48/10 settings
and readouts:
Option:
Function:
[60]
*
°C
[160]
°F
35-05 Term. X48/10 Input Type
View the temperature sensor type detected at input X48/10:
Option:
Function:
[0]
*
Not Connected
[1]
PT100 2-wire
[3]
PT1000 2-wire
[5]
PT100 3-wire
[7]
PT1000 3-wire
35-06 Temperature Sensor Alarm Function
Select the alarm function:
Option:
Function:
[0]
Off
[2]
Stop
[5]
*
Stop and trip
3.21.2 35-1* Temp. Input X48/4 (MCB 114)
35-14 Term. X48/4 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 -
10.000 s]
Enter the filter time constant. This is a
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X48/4. A high time constant
value improves dampening but also
increases the time delay through the filter.
35-15 Term. X48/4 Temp. Monitor
This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/4. The temperature limits
can be set in
35-16 Term. X48/4 Low Temp. Limit
and
Option:
Function:
[0]
*
Disabled
[1]
Enabled
35-16 Term. X48/4 Low Temp. Limit
Range:
Function:
Application
dependent
*
[Application
dependant]
Enter the minimum
temperature reading that is
expected for normal
operation of the
temperature sensor at
terminal X48/4.
35-17 Term. X48/4 High Temp. Limit
Range:
Function:
Application
dependent
*
[Application
dependant]
Enter the maximum
temperature reading that is
expected for normal
operation of the
temperature sensor at
terminal X48/4.
Parameter Descriptions
FC 300 Programming Guide
162
MG.33.MB.02 - VLT
®
is a registered Danfoss trademark
3