3.10.2 8-1* Ctrl. Word Settings
8-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid for
the fieldbus installed in slot A will be visible in the LCP display.
For guidelines in selection of
FC profile
[0] and
PROFIdrive profile
[1]
please refer to the
Serial communication via RS 485 Interface
section.
For additional guidelines in the selection of
PROFIdrive profile
[1],
ODVA
[5] and
CANopen DSP 402
[7], please refer to the Operating
Instructions for the installed fieldbus.
Option:
Function:
[0]
*
FC profile
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
[8]
MCO
8-13 Configurable Status Word STW
Option:
Function:
[0]
No function
The input is always low.
[1]
*
Profile Default
Depended on the profile set in
8-10 Control
Profile
.
[2]
Alarm 68 Only
The input will go high whenever Alarm 68 is
active and will go low whenever no alarm
68 is active
[3]
Trip excl Alarm
68
The input will go high whenever Trip on
other Alarms then Alarm 68 is active.
[10] T18 DI status
The input will go high whenever T18 has
24V and will go low whenever T18 has 0V
[11] T19 DI status
The input will go high whenever T19 has
24V and will go low whenever T19 has 0V
[12] T27 DI status
The input will go high whenever T27 has
24V and will go low whenever T27 has 0V
[13] T29 DI status
The input will go high whenever T29 has
24V and will go low whenever T29 has 0V
[14] T32 DI status
The input will go high whenever T32 has
24V and will go low whenever T32 has 0V
[15] T33 DI status
The input will go high whenever T33 has
24V and will go low whenever T33 has 0V
[16] T37 DI status
The input will go high whenever T37 has 0V
and will go low whenever T37 has 24V
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the motor,
the frequency converter, the brake resistor,
or the thermistor..
[30] Brake fault
(IGBT)
Will go high when the brake IGBT is short-
circuited.
[40] Out of ref range If Comparator 0 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
8-13 Configurable Status Word STW
Option:
Function:
[60] Comparator 0
If Comparator 0 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[61] Comparator 1
If Comparator 1 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[62] Comparator 2
If Comparator 2 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[63] Comparator 3
If Comparator 3 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[64] Comparator 4
If Comparator 4 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[65] Comparator 5
If Comparator 5 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[70] Logic Rule 0
If Logic Rule 0 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[71] Logic Rule 1
If Logic Rule 1 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[72] Logic Rule 2
If Logic Rule 2 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[73] Logic Rule 3
If Logic Rule 3 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[74] Logic Rule 4
If Logic Rule 4 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[75] Logic Rule 5
If Logic Rule 5 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[80] SL digital out A SL Controller Action. The input will go high
whenever the Smart Logic Action [38] Set
dig. out. A high is executed. The input will
go low whenever the Smart Logic Action
[32] Set dig. out. A low is executed.
[81] SL digital out B SL Controller Action. The input will go high
whenever the Smart Logic Action [39] Set
dig. out. A high is executed. The input will
go low whenever the Smart Logic Action
[33] Set dig. out. A low is executed.
[82] SL digital out C SL Controller Action. The input will go high
whenever the Smart Logic Action [40] Set
dig. out. A high is executed. The input will
go low whenever the Smart Logic Action
[34] Set dig. out. A low is executed.
[83] SL digital out D SL Controller Action. The input will go high
whenever the Smart Logic Action [41] Set
dig. out. A high is executed. The input will
go low whenever the Smart Logic Action
[35] Set dig. out. A low is executed.
[84] SL digital out E SL Controller Action. The input will go high
whenever the Smart Logic Action [42] Set
dig. out. A high is executed. The input will
Parameter Descriptions
FC 300 Programming Guide
104
MG.33.MB.02 - VLT
®
is a registered Danfoss trademark
3
3