12-32 Net Control
Option: Function:
Read only. Displays the control source in Instance 21/71.
[0]
*
Off Control via the network is not active.
[1]
On Control via the network is active
12-33 CIP Revision
Option:
Function:
Read only. Displays the CIP-version of
the option software.
[0] Major version (00 - 99)
[1] Minor version (00 - 99)
12-34 CIP Product Code
Range:
Function:
1100 (FC 302) 1110 (FC
301)
*
[0 – 9999] Read only. Displays the CIP
product code.
12-37 COS Inhibit Timer
Range:
Function:
[0 – 65.535
ms]
Read only Change-Of-State inhibit timer. If the
option is configured for COS operation, this inhibit
timer can be configured in the Forward Open
telegram to prevent that continuously changing
PCD data generates extensive network traffic. The
inhibit time is in milliseconds, 0 = disabled.
12-38 COS Filters
Range:
Function:
[[0 - 9] Filter 0 – 9
(0000 - FFFFhex)]
Change-Of-State PCD filters. Sets up a
filter mask for each word of process data
when operating in COS-mode. Single bits
in the PCD’s can be filtered in/out.
12-50 Configured Station Alias
Range:
Function:
0
*
[0 - 65535 ] The parameter shows the configured EtherCAT
station alias for the frequency converter.
Changes will first be active after a power cycle.
12-51 Configured Station Address
Range:
Function:
0
*
[0 - 65535 ] The parameter shows the configured station
address. The parameter can only be set by the
master at powerup.
12-59 EtherCAT Status
Range:
Function:
0
*
[0 - 4294967295 ] This parameter contains status information
on the EtherCAT interface. Refere to the
EtherCAT manual for detailed information.
3.13.5 12-8* Other Ethernet Services
12-80 FTP Server
Option:
Function:
[0]
*
Disable
Disables the built-in FTP server.
[1]
Enable
Enables the built-in FTP server.
12-81 HTTP Server
Option:
Function:
[0]
*
Disable
Disables the build-in HTTP (web) server.
[1]
Enable
Enables the build-in HTTP (web) server.
12-82 SMTP Service
Option:
Function:
[0]
*
Disable Disables the SMTP (e-mail) service on the option.
[1]
Enable Enables the SMTP (e-mail) service on the option.
12-89 Transent Socket Channel Port
Range:
Function:
0
*
[0 – 9999] Configures the TCP port-number for the transent
socket channel. This enables FC-telegrams to be
sent transently on Ethernet via TCP. Default value
is 4000, 0 means disabled.
3.13.6 12-9* Advanced Ethernet Settings
12-90 Cable Diagnostics
Option:
Function:
Enables/disables advanced Cable diagnosis function.
If enabled, the distance to cable errors can be read
out in
12-93 Cable Error Length
. The parameter
resumes to the default setting of Disable after the
diagnostics have finished.
[0]
*
Disable
[1]
Enable
NOTE
The cable diagnostics function will only be issued on ports
where there is no link (see
12-10 Link Status
,
Link Status
)
12-91 Auto Cross-Over
Option:
Function:
[0]
Disable
Disables the auto cross-over function.
[1]
*
Enable
Enables the auto cross-over function.
NOTE
Disabling of the auto cross-over function will require crossed
Ethernet cables for daisy-chaining the options.
12-92 IGMP Snooping
Option:
Function:
This prevents flooding of the Ethernet protocol stack
by only forwarding multicast packets to ports that
are a member of the multicast group
[0]
Disable Disables the IGMP snooping function.
Parameter Descriptions
FC 300 Programming Guide
MG.33.MB.02 - VLT
®
is a registered Danfoss trademark
123
3
3