14-90 Fault Level
Option:
Function:
[0]
*
Off
Use this parameter to customize Fault levels. Use
[0] "Off" with caution as it will ignore all Warnings
& Alarms for the chosen source.
14-90 Fault Level
Option:
Function:
[1]
Warning
[2]
Trip
[3]
Trip Lock
Failure
Alarm
Off
Warning
Trip
Trip Lock
10V low
1
X
D
24V low
47
X
D
1.8V supply low
48
X
D
Voltage limit
64
X
D
Earth fault during ramping
14
D
X
Earth fault 2 during cont.
operation
45
D
X
Torque Limit
12
X
D
Over Current
13
X
D
Short Circuit
16
X
D
Heatsink temperature
29
X
D
Heatsink sensor
39
X
D
Control card temperature
65
X
D
Power card temperature
6
2)
X
D
Heatsink temperature
1)
244
X
D
Heatsink sensor
1)
245
X
D
Power card temperature
1)
247
Table 3.3 Table for Selection of Choice of Action when Selected Alarm Appears
D = Default setting. x = possible selection.
1) Only high power drives
In FC small and medium A69 is only a warning
Parameter Descriptions
FC 300 Programming Guide
MG.33.MB.02 - VLT
®