3.7 Parameters: 5-** Digital In/Out
3.7.1 5-0* Digital I/O Mode
Parameters for configuring the input and output using NPN
and PNP.
These parameters cannot be adjusted while motor is
running.
5-00 Digital I/O Mode
Option:
Function:
Digital inputs and programmed digital outputs are pre-
programmable for operation either in PNP or NPN
systems.
[0]
*
PNP Action on positive directional pulses
(↕)
. PNP systems
are pulled down to GND.
[1]
NPN Action on negative directional pulses
(↕)
. NPN systems
are pulled up to + 24V, internally in the frequency
converter.
NOTE
Once this parameter has been changed, it must be activated
by performing a power cycle.
5-01 Terminal 27 Mode
Option:
Function:
[0]
*
Input
Defines terminal 27 as a digital input.
[1]
Output
Defines terminal 27 as a digital output.
5-02 Terminal 29 Mode
Option:
Function:
[0]
*
Input
Defines terminal 29 as a digital input.
[1]
Output
Defines terminal 29 as a digital output.
This parameter is available for FC 302 only.
3.7.2 Digital Inputs
The digital inputs are used for selecting various functions in
the frequency converter. All digital inputs can be set to the
following functions:
Digital input function
Select
Terminal
No operation
[0]
All *term 32, 33
Reset
[1]
All
Coast inverse
[2]
All *term 27
Coast and reset inverse
[3]
All
Quick stop inverse
[4]
All
DC-brake inverse
[5]
All
Stop inverse
[6]
All
Start
[8]
All *term 18
Latched start
[9]
All
Digital input function
Select
Terminal
Reversing
[10]
All *term 19
Start reversing
[11]
All
Enable start forward
[12]
All
Enable start reverse
[13]
All
Jog
[14]
All *term 29
Preset reference on
[15]
All
Preset ref bit 0
[16]
All
Preset ref bit 1
[17]
All
Preset ref bit 2
[18]
All
Freeze reference
[19]
All
Freeze output
[20]
All
Speed up
[21]
All
Speed down
[22]
All
Set-up select bit 0
[23]
All
Set-up select bit 1
[24]
All
Precise stop inverse
[26]
18, 19
Precises start, stop
[27]
18, 19
Catch up
[28]
All
Slow down
[29]
All
Counter input
[30]
29, 33
Pulse input Edge Trigged
[31]
29, 33
Pulse input Time Based
[32]
29, 33
Ramp bit 0
[34]
All
Ramp bit 1
[35]
All
Latched precise start
[40]
18, 19
Latched precise stop
inverse
[41]
18, 19
External interlock
[51]
DigiPot Increase
[55]
All
DigiPot Decrease
[56]
All
DigiPot Clear
[57]
All
Digipot Hoist
[58]
All
Counter A (up)
[60]
29, 33
Counter A (down)
[61]
29, 33
Reset Counter A
[62]
All
Counter B (up)
[63]
29, 33
Counter B (down)
[64]
29, 33
Reset Counter B
[65]
All
Mech. Brake Feedb.
[70]
All
Mech. Brake Feedb. Inv.
[71]
All
PID Error Inv.
[72]
All
PID Reset I-part
[73]
All
PID enable
[74]
All
PTC Card 1
[80]
All
FC 300 standard terminals are 18, 19, 27, 29, 32 and 33. MCB
101 terminals are X30/2, X30/3 and X30/4.
Terminal 29 functions as an output only in FC 302.
Functions dedicated to only one digital input are stated in
the associated parameter.
Parameter Descriptions
FC 300 Programming Guide
70
MG.33.MB.02 - VLT
®
is a registered Danfoss trademark