13-11 Comparator Operator
Array [6]
Option:
Function:
Select the operator to be used in the
comparison. This is an array parameter
containing comparator operators 0 to 5.
[0]
<
Select < [0] for the result of the evaluation to
be TRUE, when the variable selected in
is smaller than the
fixed value in
13-12 Comparator Value
. The
result will be FALSE, if the variable selected in
is greater than the
fixed value in
13-12 Comparator Value
.
[1]
*
≈ (equal)
Select ≈ [1] for the result of the evaluation to
be TRUE, when the variable selected in
is approximately
equal to the fixed value in
13-12 Comparator
Value
.
[2]
>
Select > [2] for the inverse logic of option <
[0].
[5]
TRUE longer
than..
[6]
FALSE
longer
than..
[7]
TRUE
shorter
than..
[8]
FALSE
shorter
than..
13-12 Comparator Value
Array [6]
Range:
Function:
Size related
*
[-100000.000 -
100000.000 ]
Enter the ‘trigger level’ for the
variable that is monitored by
this comparator. This is an array
parameter containing
comparator values 0 to 5.
3.14.4 13-2* Timers
Use the result (TRUE or FALSE) from
timers
directly to define
an
event
(see
13-51 SL Controller Event
), or as boolean input in
a
logic rule
(see
13-40 Logic Rule Boolean 1
,
13-42 Logic Rule
Boolean 2
or
13-44 Logic Rule Boolean 3
). A timer is only FALSE
when started by an action (i.e. Start timer 1 [29]) until the
timer value entered in this parameter is elapsed. Then it
becomes TRUE again.
All parameters in this parameter group are array parameters
with index 0 to 2. Select index 0 to program Timer 0, select
index 1 to program Timer 1, and so on.
13-20 SL Controller Timer
Range:
Function:
Application
dependent
*
[Application
dependant]
Enter the value to define the
duration of the FALSE output
from the programmed timer. A
timer is only FALSE if it is started
by an action (i.e.
Start timer 1 [29]
)
and until the given timer value
has elapsed.
3.14.5 13-4* Logic Rules
Combine up to three boolean inputs (TRUE / FALSE inputs)
from timers, comparators, digital inputs, status bits and
events using the logical operators AND, OR, and NOT. Select
boolean inputs for the calculation in
13-40 Logic Rule Boolean
1
,
13-42 Logic Rule Boolean 2
and
13-44 Logic Rule Boolean 3
.
Define the operators used to logically combine the selected
inputs in
and
.
. . .
. . .
. . .
. . .
Par. 13-43
Logic Rule Operator 2
Par. 13-41
Logic Rule Operator 1
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-44
Logic Rule Boolean 3
130BB673.10
Priority of calculation
The results of
13-40 Logic Rule Boolean 1
,
and
13-42 Logic Rule Boolean 2
are calculated first.
The outcome (TRUE / FALSE) of this calculation is combined
with the settings of
and
13-44 Logic Rule Boolean 3
, yielding the final result (TRUE /
FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[0]
*
False
Select the first boolean (TRUE or
FALSE) input for the selected logic
rule.
See
([0] - [61]) and
([70] - [75]) for
further description.
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current limit
[7]
Out of current range
[8]
Below I low
Parameter Descriptions