3.13.3 12-2* Process Data
12-20 Control Instance
Range:
Function:
[None, 20, 21, 100,
101, 103]
Read only. Displays the originator-to-
target connection point. If no CIP
connection is present “None” is displayed.
12-21 Process Data Config Write
Range:
Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
NOTE
For configuration of 2-word (32-bit) parameter read/write,
use 2 consecutive arrays in
12-21 Process Data Config Write
and
12-22 Process Data Config Read
.
12-22 Process Data Config Read
Range:
Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
12-23 Process Data Config Write Size
Range:
Function:
16
*
[1 - 32 ] Sets the number of bits being sent from the drive
as process data. The setting counts from right
(LSB). The value 1 means that only the least
significant bit of the signal will be transferred from
the drive.
12-24 Process Data Config Read Size
Range:
Function:
16
*
[1 - 32 ] Sets the number of bits being sent to the drive as
process data. The setting counts from right (LSB).
The value 1 means that only the least significant bit
of the signal will be transferred to the drive. The
preceding bits will be set to zero.
12-27 Primary Master
Range:
Function:
0
*
[0 -
4294967295 ]
Controls the Master’s access to the process
data. The value zero (0.0.0.0) means that
other masters can take control of the drive
immediately if the connection is lost or
closed. Setting an IP number means that only
a master with this value can establish a
connection for controlling the drive. In
systems with backup masters, this parameter
should be left to the value zero (0.0.0.0).
12-28 Store Data Values
Option:
Function:
This parameter activates a function that stores all
parameter values in the non-volatile memory
(EEPROM) thus retaining parameter values at
power-down.
The parameter returns to “Off”.
[0]
*
Off
The store function is inactive.
[1]
Store All
set-ups
All parameter value will be stored in the non-
volatile memory, in all four setups.
12-29 Store Always
Option: Function:
Activates function that will always store received
parameter data in non-volatile memory (EEPROM).
[0]
*
Off
[1]
On
3.13.4 12-3* EtherNet/IP
12-30 Warning parameter
Range:
Function:
[0000 –
FFFF hex]
Read only. Displays the EtherNet/IP specific 16-bit
Status-word.
Bit
Description
0
Owned
1
Not used
2
Configured
3
Not used
4
Not used
5
Not used
6
Not used
7
Not used
8
Minor recoverable fault
9
Minor unrecoverable fault
10
Major recoverable fault
11
Major unrecoverable fault
12
Not used
13
Not used
14
Not used
15
Not used
12-31 Net Reference
Option: Function:
Read only. Displays the reference source in Instance
21/71.
[0]
*
Off Reference from the network is not active.
[1]
On Reference from the network is active.
Parameter Descriptions
FC 300 Programming Guide
122
MG.33.MB.02 - VLT
®
is a registered Danfoss trademark