6-50 Terminal 42 Output
Option:
Function:
[101] Reference
[Min - Max] 0% = 0mA;
100% = 20mA
[-Max - Max] -100% =
0mA; 0% = 10mA; +100% = 20mA
[102] Feedback
[103] Motor
current
Value is taken from
.
Inverter max. current (160% current) is equal to
20mA.
Example: Inverter norm current (11kW) = 24A.
160% = 38.4A. Motor norm current = 22A
Read-out 11.46mA.
20
mA x 22 A
38.4
A
= 11.46
mA
In case the norm motor current is equal to
20mA, the output setting of
is:
IVLTMax x 100
IMotorNorm
= 38.4 x 100
22
= 175 %
[104] Torque rel
to limit
The torque setting is related to setting in
[105] Torq relate
to rated
The torque is related to the motor torque
setting.
[106] Power
Taken from
[107] Speed
Taken from
. 20mA =
value in
[108] Torque
Torque reference related to 160% torque.
[109] Max Out
Freq
0Hz = 0mA,
= 20mA.
[113] PID
Clamped
Output
[119] Torque %
lim
[130] Output
freq.
4-20mA
0Hz = 4mA, 100Hz = 20mA
[131] Reference
4-20mA
[Min-Max] 0% = 4mA;
100% = 20mA
[-Max-Max] -100% = 4mA;
0% = 12mA; +100% = 20mA
[132] Feedback
4-20mA
[133] Motor cur.
4-20mA
Value is taken from
.
Inverter max. current (160% current) is equal to
20mA.
Example: Inverter norm current (11kW) = 24A.
160% = 38.4A. Motor norm current = 22A
Read-out 11.46mA.
16
mA x 22 A
38.4
A
+ 4
mA = 13.17 mA
6-50 Terminal 42 Output
Option:
Function:
In case the norm motor current is equal to
20mA, the output setting of
is:
IVLTMax x 100
IMotorNorm
= 38.4 x 100
22
= 175 %
[134] Torq.% lim
4-20 mA
The torque setting is related to setting in
[135] Torq.%
nom 4-20
mA
The torque setting is related to the motor
torque setting.
[136] Power
4-20mA
Taken from
[137] Speed
4-20mA
Taken from
. 20mA =
Value in
.
[138] Torque
4-20mA
Torque reference related to 160% torque.
[139] Bus ctrl.
0-20 mA
An output value set from fieldbus process data.
The output will work independently of internal
functions in the frequency converter.
[140] Bus ctrl.
4-20 mA
An output value set from fieldbus process data.
The output will work independently of internal
functions in the frequency converter.
[141] Bus ctrl
0-20mA t.o.
defines the
behaviour of the analog output in case of bus
time-out.
[142] Bus ctrl
4-20mA t.o.
defines the
behaviour of the analog output in case of bus
time-out.
[149] Torque %
lim 4-20mA
Analogue output at zero torque = 12mA.
Motoric torque will increase the output current
to max torque limit 20mA (set in
).
Generative torque will decrease the output to
torque limit Generator Mode (set in
4-17 Torque Limit Generator Mode
)
Ex:
: 200% and
4-17 Torque Limit Generator Mode
: 200%. 20mA
= 200% Motoric and 4mA = 200% Generatoric.
0mA
12 mA
20 mA
4mA
Par 4-17
(200%)
Par 4-16
(200%)
0% Torque
130BB372.10
[150] Max Out Fr
4-20mA
0hz = 0mA,
= 20mA.
Parameter Descriptions
FC 300 Programming Guide
MG.33.MB.02 - VLT
®
is a registered Danfoss trademark
91