6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0.000
*
[-999999.999 -
999999.999 ]
Enter the analog input scaling value
that corresponds to the low
voltage/low current set in
6-10 Terminal 53 Low Voltage
and
6-12 Terminal 53 Low Current
.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
Application
dependent
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Enter the analog input
scaling value that
corresponds to the
maximum reference
feedback value set in
and
.
6-16 Terminal 53 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 -
10.000 s]
Enter the time constant. This is a first-order
digital low pass filter time constant for
suppressing electrical noise in terminal 53.
A high time constant value improves
dampening but also increases the time
delay through the filter.
This parameter cannot be adjusted while
the motor is running.
3.8.3 6-2* Analog Input 2
Parameters for configuring the scaling and limits for analog
input 2 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
Function:
0.07 V
*
[Application
dependant]
Enter the low voltage value. This
analog input scaling value should
correspond to the minimum reference
value, set in
.
See also the section
Reference
Handling
.
6-21 Terminal 54 High Voltage
Range:
Function:
10.00 V
*
[par. 6-20 -
10.00 V]
Enter the high voltage value. This analog
input scaling value should correspond to
the high reference/feedback value set in
6-25 Terminal 54 High Ref./Feedb. Value
.
6-22 Terminal 54 Low Current
Range:
Function:
0.14
mA
*
[Application
dependant]
Enter the low current value. This
reference signal should correspond to
the minimum reference value, set in
. The value
must be set at >2mA in order to
activate the Live Zero Time-out
Function in
6-23 Terminal 54 High Current
Range:
Function:
20.00 mA
*
[par. 6-22 -
20.00 mA]
Enter the high current value
corresponding to the high reference/
feedback value set in
6-25 Terminal 54
High Ref./Feedb. Value
.
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
Function:
0 ReferenceFeed-
backUnit
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Enter the analog input
scaling value that
corresponds to the
minimum reference
feedback value set in
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
Application
dependent
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Enter the analog input
scaling value that
corresponds to the
maximum reference
feedback value set in
6-26 Terminal 54 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 -
10.000 s]
Enter the time constant. This is a first-order
digital low pass filter time constant for
suppressing electrical noise in terminal 54.
A high time constant value improves
dampening but also increases the time
delay through the filter.
This parameter cannot be adjusted while
the motor is running.
Parameter Descriptions
FC 300 Programming Guide
MG.33.MB.02 - VLT
®
is a registered Danfoss trademark
89