16-37 Inv. Max. Current
Range:
Function:
Application
dependent
*
[0.01 -
10000.00 A]
View the inverter maximum
current, which should match the
nameplate data on the
connected motor. The data are
used for calculation of torque,
motor protection, etc.
16-38 SL Controller State
Range:
Function:
0
*
[0 - 100 ] View the state of the event under execution by the
SL controller.
16-39 Control Card Temp.
Range:
Function:
0 C
*
[0 - 100 C] View the temperature on the control card,
stated in
°
C
16-40 Logging Buffer Full
Option: Function:
View whether the logging buffer is full (see parameter
group 15-1*). The logging buffer will never be full when
is set to
Log always
[0].
[0]
*
No
[1]
Yes
16-49 Current Fault Source
Range:
Function:
0
*
[0 - 8 ] Value indicates source of current faults including
short circuit, over current, and phase imbalance
(from left):
1-4 Inverter
5-8 Rectifier
0 No fault recorded
3.17.4 16-5* Ref. & Feedb.
16-50 External Reference
Range:
Function:
0.0
*
[-200.0 - 200.0 ] View the total reference, the sum of digital,
analog, preset, bus and freeze references,
plus catch-up and slow-down.
16-51 Pulse Reference
Range:
Function:
0.0
*
[-200.0 -
200.0 ]
View the reference value from programmed
digital input(s). The read-out can also reflect
the impulses from an incremental encoder.
16-52 Feedback [Unit]
Range:
Function:
0.000 Reference-
FeedbackUnit
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
View the feedback unit
resulting from the
selection of unit and
scaling in
,
and
.
16-53 Digi Pot Reference
Range:
Function:
0.00
*
[-200.00 - 200.00 ] View the contribution of the Digital
Potentiometer to the actual reference.
16-57 Feedback [RPM]
Range:
Function:
0 RPM
*
[-30000 -
30000 RPM]
Read-out parameter where the actual
motor RPM from the feed-back source can
be read in both closed loop and open
loop. The feed-back source is selected by
7-00 Speed PID Feedback Source
.
Parameter Descriptions
FC 300 Programming Guide
152
MG.33.MB.02 - VLT
®