5.2 Final optimization and test
5.2.1 Final optimization and test
To optimize motor shaft performance and optimize the adjustable frequency drive for the connected motor and installation, please follow these steps:
Ensure that the adjustable frequency drive and the motor are connected, and power is applied to the adjustable frequency drive.
NOTE!
Before power-up, ensure that connected equipment is ready for use.
Step 1. Locate motor nameplate.
NOTE!
The motor is either star- (Y) or delta-connected (
Δ
). This information is located on the motor nameplate data.
Figure 5.56: Motor nameplate example
Step 2. Enter the motor nameplate data in the following param-
eter list.
To access the list, first press [QUICK MENU] key, then select “Q2 Quick
Set-up.”
1.
Motor Power [kW]
or Motor Power [HP]
par. 1-20
par. 1-21
2.
Motor Voltage
par. 1-22
3.
Motor Frequency
par. 1-23
4.
Motor Current
par. 1-24
5.
Motor Nominal Speed
par. 1-25
Table 5.8: Motor related parameters
VLT
®
AQUA Drive
Instruction Manual
5 Electrical installation
MG.20.M5.22 - VLT
®
is a registered Danfoss trademark
5-29