[1006]
Readout Receive Error Counter
View the number of CAN control receipt errors since the last power-up.
[1007]
Readout Bus-off Counter
View the number of bus-off events since the last power-up.
[1013]
Warning Parameter
View a DeviceNet-specific warning word. One separate bit is assigned to every warning.
[1115]
LON Warning Word
Shows the LON-specific warnings.
[1117]
XIF Revision
Shows the version of the external interface file of the Neuron C chip on the LON option.
[1118]
LON Works Revision
Shows the software version of the application program of the Neuron C chip on the LON option.
[1500]
Operating Hours
View the number of running hours of the adjustable frequency drive.
[1501]
Running Hours
View the number of running hours of the motor.
[1502]
kWh Counter
View the line power consumption in kWh.
[1600]
Control Word
View the control word sent from the adjustable frequency drive via the serial communication port
in hex code.
[1601] *
Reference [Unit]
Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) in selected
unit.
[1602]
Reference %
Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) as a per-
centage.
[1603]
Status Word
Present status word
[1605]
Main Actual Value [%]
One or more warnings in a Hex code
[1609]
Custom Readout
View the user-defined readouts as defined in par. 0-30, 0-31 and 0-32.
[1610]
Power [kW]
Actual power consumed by the motor in kW.
[1611]
Power [hp]
Actual power consumed by the motor in HP.
[1612]
Motor Voltage
Voltage supplied to the motor.
[1613]
Motor Frequency
Motor frequency, i.e., the output frequency from the adjustable frequency drive in Hz.
[1614]
Motor Current
Phase current of the motor measured as effective value.
[1615]
Frequency [%]
Motor frequency, i.e., the output frequency from the adjustable frequency drive as a percentage.
[1616]
Torque [Nm]
Present motor load as a percentage of the rated motor torque.
[1617]
Speed [RPM]
Speed in RPM (revolutions per minute), i.e., the motor shaft speed in closed-loop based on the
entered motor nameplate data, the output frequency and the load on the adjustable frequency drive.
[1618]
Motor Thermal
Thermal load on the motor, calculated by the ETR function. See also parameter group 1-9* Motor
Temperature.
[1622]
Torque [%]
Shows the actual torque produced as a percentage.
[1630]
DC Link Voltage
Intermediate circuit voltage in the adjustable frequency drive.
[1632]
BrakeEnergy/s
Present braking energy transferred to an external brake resistor.
Stated as an instantaneous value.
[1633]
BrakeEnergy/2 min
Braking energy transferred to an external brake resistor. The mean power is calculated continuously
for the latest 120 seconds.
[1634]
Heatsink Temp.
Present heatsink temperature of the adjustable frequency drive. The cut-out limit is 203 ± 9°F (95
± 5°C); cutting back in occurs at 158 ± 9°F (70 ± 5°C).
[1635]
Thermal Drive Load
Percentage load of the inverters
[1636]
Inv. Nom. Current
Nominal current of the adjustable frequency drive.
[1637]
Inv. Max. Current
Maximum current of the adjustable frequency drive.
[1638]
SL Control State
State of the event executed by the control.
[1639]
Control Card Temp.
Temperature of the control card.
[1650]
External Reference
Sum of the external reference as a percentage, i.e., the sum of analog/pulse/bus.
[1652]
Feedback [Unit]
Signal value in units from the programmed digital input(s).
[1653]
Digi Pot Reference
View the contribution of the digital potentiometer to the actual reference feedback.
8 How to program the adjustable frequency
drive
VLT
®
AQUA Drive
Instruction Manual
8-10
MG.20.M5.22 - VLT
®
is a registered Danfoss trademark
8