Adjustable
frequency
drive
Bussmann
Bussmann
Bussmann
SIBA
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
380–480 V, 525–600 V
kW
Type RK1
Type J
Type T
Type RK1
Type RK1
Type CC
Type RK1
K37-1K1
KTS-R6
JKS-6
JJS-6
5017906-006
KLS-R6
ATM-R6
A6K-6R
1K5-2K2
KTS-R10
JKS-10
JJS-10
5017906-010
KLS-R10
ATM-R10
A6K-10R
3K0
KTS-R15
JKS-15
JJS-15
5017906-016
KLS-R16
ATM-R16
A6K-16R
4K0
KTS-R20
JKS-20
JJS-20
5017906-020
KLS-R20
ATM-R20
A6K-20R
5K5
KTS-R25
JKS-25
JJS-25
5017906-025
KLS-R25
ATM-R25
A6K-25R
7K5
KTS-R30
JKS-30
JJS-30
5012406-032
KLS-R30
ATM-R30
A6K-30R
11K
KTS-R40
JKS-40
JJS-40
5014006-040
KLS-R40
-
A6K-40R
15K
KTS-R40
JKS-40
JJS-40
5014006-040
KLS-R40
-
A6K-40R
18K
KTS-R50
JKS-50
JJS-50
5014006-050
KLS-R50
-
A6K-50R
22K
KTS-R60
JKS-60
JJS-60
5014006-063
KLS-R60
-
A6K-60R
30K
KTS-R80
JKS-80
JJS-80
2028220-100
KLS-R80
-
A6K-80R
37K
KTS-R100
JKS-100
JJS-100
2028220-125
KLS-R100
A6K-100R
45K
KTS-R125
JKS-150
JJS-150
2028220-125
KLS-R125
A6K-125R
55K
KTS-R150
JKS-150
JJS-150
2028220-160
KLS-R150
A6K-150R
75K
FWH-220
-
-
2028220-200
L50S-225
A50-P225
90K
FWH-250
-
-
2028220-250
L50S-250
A50-P250
Table 5.4: UL fuses 380–600 V
KTS fuses from Bussmann may substitute for KTN for 240 V adjustable frequency drives.
FWH fuses from Bussmann may substitute for FWX for 240 V adjustable frequency drives.
KLSR fuses from LITTEL FUSE may substitute for KLNR fuses for 240 V adjustable frequency drives.
L50S fuses from LITTEL FUSE may substitute for L50S fuses for 240 V adjustable frequency drives.
A6KR fuses from FERRAZ SHAWMUT may substitute for A2KR for 240 V adjustable frequency drives.
A50X fuses from FERRAZ SHAWMUT may substitute for A25X for 240 V adjustable frequency drives.
5.1.4 Grounding and IT line power
The ground connection cable cross-section must be at least 0.016 in
2
[10 mm
2
] or two rated line power wires terminated separately
according to
EN 50178 or IEC 61800-5-1
, unless national regulations specify differently. Always comply with national and local regu-
lations on cable cross-sections.
The line power is connected to the main disconnect switch if this is included.
NOTE!
Make sure that the AC line voltage corresponds to the AC line voltage of the adjustable frequency drive nameplate.
Figure 5.5: Terminals for line power and grounding.
5 Electrical installation
VLT
®
AQUA Drive
Instruction Manual
5-4
MG.20.M5.22 - VLT
®
is a registered Danfoss trademark
5