6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A* [-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the low voltage/low current set in par.
6-10
Terminal 53 Low Voltage
and par. 6-12
Terminal 53 Low Current
.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
50.000 N/
A*
[-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the high voltage/high current value set in
par.6-11
Terminal 53 High Voltage
and par. 6-13
Terminal 53 High Current
.
6-20 Terminal 54 Low Voltage
Range:
Function:
0.07 V*
[0.00 - par. 6-21 V]
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value, set in par.6-24
Terminal 54 Low Ref./Feedb. Value
.
6-21 Terminal 54 High Voltage
Range:
Function:
10.00 V*
[par. 6-20 - 10.00 V]
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par.6-25
Terminal 54 High Ref./Feedb. Value
.
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A* [-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the low voltage/low current value set in
par.6-20
Terminal 54 Low Voltage
and par. 6-22
Terminal 54 Low Current
.
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
100.000 N/
A*
[-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the high voltage/high current value set in
par.6-21
Terminal 54 High Voltage
and par. 6-23
Terminal 54 High Current
.