The parameters can be accessed immediately unless a password has been created via par. 0-60
Main Menu Password
, par. 0-61
Access to Main Menu
w/o Password
, par. 0-65
Personal Menu Password
or par. 0-66
Access to Personal Menu w/o Password
.
Quick Set-up
is used to set up the adjustable frequency drive using only the most essential parameters.
The parameter values can be changed using the up/down arrows when the value is flashing.
Select the main menu by pressing the [Menu] key a number of times until the main menu LED is lit.
Select the parameter group [xx-__] and press [OK].
Select the parameter [__-xx] and press [OK].
If the parameter is an array parameter, select the array number and press [OK].
Select the desired data value and press [OK].
Navigation Keys
[Back]
for stepping backwards
Arrow [
▲
] [
▼
]
keys are used for navigating between parameter groups, parameters and
within parameters.
[OK]
is used for choosing a parameter marked by the cursor and for enabling
the change of a parameter.
130BP079.10
Figure 7.4: Display example
Operation Keys
Keys for local control are found at the bottom of the control panel.
130BP046.10
Figure 7.5: Operation keys of the numerical LCP (NLCP)
[Hand on]
enables control of the adjustable frequency drive via the LCP. [Hand on] also starts the motor and makes it possible to enter the motor speed data by
means of the arrow keys. The key can be
Enabled
[1] or
Disabled
[0] via par. 0-40
[Hand on] Key on LCP
.
External stop signals activated by means of control signals or a serial bus will override a 'start' command via the LCP.
The following control signals will still be active when [Hand on] is activated:
•
[Hand on] - [Off] - [Auto on]
•
Reset
•
Coasting stop inverse
•
Reversing
•
Set-up select lsb - Set-up select msb
•
Stop command from serial communication
•
Quick stop
•
DC brake
[Off]
stops the connected motor. The key can be
Enabled
[1] or
Disabled
[0] via par. 0-41
[Off] Key on LCP
.
If no external stop function is selected and the [Off] key is inactive, the motor can be stopped by disconnecting the line power supply.
[Auto on]
enables the adjustable frequency drive to be controlled via the control terminals and/or serial communication. When a start signal is applied to the control
terminals and/or the bus, the adjustable frequency drive will start. The key can be
Enabled
[1] or
Disabled
[0] via par. 0-42
[Auto on] Key on LCP
.
VLT
®
AQUA Drive
Instruction Manual
7 How to operate the adjustable frequency
drive
MG.20.M5.22 - VLT
®
is a registered Danfoss trademark
7-7