5-53 Term. 29 High Ref./Feedb. Value
Range:
Function:
100.000 N/
A*
[-999999.999 - 999999.999 N/A]
Enter the high reference value [RPM] for the motor shaft speed and the high feedback value, see
also par. 5-58
Term. 33 High Ref./Feedb. Value
.
8.2.8 6-** Analog In/Out
Parameter group for configuring the analog input and output.
6-00 Live Zero Timeout Time
Range:
Function:
10 s*
[1 - 99 s]
Enter the Live Zero Timeout time period. Live Zero Timeout Time is active for analog inputs, (i.e.,
terminal 53 or terminal 54), allocated to current and used as reference or feedback sources. If the
reference signal value associated with the selected current input falls below 50% of the value set
in par.6-10
Terminal 53 Low Voltage
, par. 6-12
Terminal 53 Low Current
, par.6-20
Terminal 54 Low
Voltage
or par. 6-22
Terminal 54 Low Current
for a time period longer than the time set in par.
6-00
Live Zero Timeout Time
, the function selected in par.6-01
Live Zero Timeout Function
will be
activated.