Alarm Word and Extended Status Word
Bit
Hex
Dec
Alarm Word
Warning Word
Extended Status Word
0
00000001
1
Brake Check
Brake Check
Ramping
1
00000002
2
Pwr. Card Temp
Pwr. Card Temp
AMA Running
2
00000004
4
Earth Fault
Earth Fault
Start CW/CCW
3
00000008
8
Ctrl.Card Temp
Ctrl.Card Temp
Slow Down
4
00000010
16
Ctrl. Word TO
Ctrl. Word TO
Catch Up
5
00000020
32
Over Current
Over Current
Feedback High
6
00000040
64
Torque Limit
Torque Limit
Feedback Low
7
00000080
128
Motor Th Over
Motor Th Over
Output Current High
8
00000100
256
Motor ETR Over
Motor ETR Over
Output Current Low
9
00000200
512
Inverter Overld.
Inverter Overld.
Output Freq High
10
00000400
1024
DC under Volt
DC under Volt
Output Freq Low
11
00000800
2048
DC over Volt
DC over Volt
Brake Check OK
12
00001000
4096
Short Circuit
DC Voltage Low
Braking Max
13
00002000
8192
Inrush Fault
DC Voltage High
Braking
14
00004000
16384
Mains ph. Loss
Mains ph. Loss
Out of Speed Range
15
00008000
32768
AMA Not OK
No Motor
OVC Active
16
00010000
65536
Live Zero Error
Live Zero Error
17
00020000
131072
Internal Fault
10V Low
18
00040000
262144
Brake Overload
Brake Overload
19
00080000
524288
U phase Loss
Brake Resistor
20
00100000
1048576
V phase Loss
Brake IGBT
21
00200000
2097152
W phase Loss
Speed Limit
22
00400000
4194304
Fieldbus Fault
Fieldbus Fault
23
00800000
8388608
24 V Supply Low
24V Supply Low
24
01000000
16777216
Mains Failure
Mains Failure
25
02000000
33554432
1.8V Supply Low
Current Limit
26
04000000
67108864
Brake Resistor
Low Temp
27
08000000
134217728
Brake IGBT
Voltage Limit
28
10000000
268435456
Option Change
Unused
29
20000000
536870912
Drive Initialised
Unused
30
40000000
1073741824
Safe Stop
Unused
Table 9.2: Description of Alarm Word, Warning Word and Extended Status Word
The alarm words, warning words and extended status words can be read out via serial bus or optional fieldbus for diagnosis. See also par. 16-90, 16-92
and 16-94.
9.1.1 Fault messages
WARNING 1, 10 Volts low:
The 10 V voltage from terminal 50 on the control card is below 10 V.
Remove a portion of the load from terminal 50, as the 10 v supply is
overloaded. Max. 15 mA or minimum 590
Ω
.
WARNING/ALARM 2, Live zero error:
The signal on terminal 53 or 54 is less than 50% of the value set in par.
6-10
Terminal 53 Low Voltage
, par. 6-12
Terminal 53 Low Current
, par.
6-20
Terminal 54 Low Voltage
, or par. 6-22
Terminal 54 Low Current
respectively.
WARNING/ALARM 3, No motor:
No motor has been connected to the output of the adjustable frequency
drive.
WARNING/ALARM 4, Line phase loss:
A phase is missing on the supply side, or the AC line voltage imbalance
is too high.
This message also appears in case of a fault in the input rectifier on the
adjustable frequency drive.
Check the supply voltage and supply currents to the adjustable frequency
drive.
WARNING 5, DC link voltage high:
The intermediate circuit voltage (DC) is higher than the overvoltage limit
of the control system. The adjustable frequency drive is still active.
WARNING 6, DC link voltage low:
The intermediate circuit voltage (DC) is below the undervoltage limit of
the control system. The adjustable frequency drive is still active.
WARNING/ALARM 7, DC overvoltage:
If the intermediate circuit voltage exceeds the limit, the adjustable fre-
quency drive trips after a given period of time.
Possible corrections:
Select
O
ver
V
oltage
C
ontrol function in par. 2-17
Over-voltage
Control
Connect a brake resistor
Extend the ramp time
Activate functions in par. 2-10
Brake Function
Increase par. 14-26
Trip Delay at Inverter Fault
Selecting the OVC function will extend the ramp times.
VLT
®
AQUA Drive
Instruction Manual
9 Troubleshooting
MG.20.M5.22 - VLT
®
is a registered Danfoss trademark
9-3
9