Troubleshooting by Indication on the Remote Controller
355
When using the digital type of multiple tester, make
measurement in diode check mode (
)
No.
Measuring
point
Judgement
Criteria
Remarks
+
–
1
P2
U
1.2V and more
Due to condenser charge and
so on, resistance
measurement may require
some time.
2
P2
V
3
P2
W
4
U
P2
0.3 ~ 0.7V
5
V
P2
6
W
P2
7
N3
U
8
N3
V
9
N3
W
10
U
N3
1.2V and more
Due to condenser charge and
so on, resistance
measurement may require
some time.
11
V
N3
12
W
N3