Troubleshooting by Indication on the Remote Controller
142
Troubleshooting
Refer to P.369.
YES
NO
Discharge pipe
temperature is 115˚C
or higher.
Are the
characteristics of
the discharge pipe
thermistor normal?
NO
YES
Refrigerant
shortage,
compression
defect, etc.
Defective
refrigerant
system.
Replace the
discharge pipe
thermistor.
Replace the
outdoor unit
PCB.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
CHECK 11
CHECK 11