![background image](http://html1.mh-extra.com/html/daikin/vrvii/vrvii_manual_4705257375.webp)
Troubleshooting by Indication on the Remote Controller
370
For outdoor air thermistor
For suction pipe thermistor
For heat exchanger thermistor
For intermediate heat exchanger thermistor
For liquid thermistor
For remote controller thermistor
T°C
k
Ω
T°C
k
Ω
-30
361.7719
40
10.6281
-25
265.4704
45
8.7097
-20
196.9198
50
7.1764
-15
147.5687
55
5.9407
-10
111.6578
60
4.9439
-5
85.2610
65
4.1352
0
65.6705
70
3.4757
5
50.9947
75
2.9349
10
39.9149
80
2.4894
15
31.4796
85
2.1205
20
25.0060
90
1.8138
25
20.0000
95
1.5575
30
16.1008
100
1.3425
35
13.0426
105
1.1614
3SA48001 (AD87A001J)