Troubleshooting by Indication on the Remote Controller
346
Check for causes of rise in high
pressure
Referring to the Fault Tree Analysis (FTA) shown below,
probe the defective points.
CHECK 1
Rise in
high
pressure
[In cooling]
If the outdoor
unit electronic
expansion valve
is throttled:
(
∗
1.)
[In heating]
If the indoor
unit electronic
expansion
valve
excessively
throttled:
(
∗
2.)
Stop valve
closed
Bent or
crashed pipe
High pipe
resistance
Local pressure
rise
Defective high
pressure
control
Clogging of
foreign
materials
Defective
valve coil
Defective
outdoor unit
electronic
expansion
valve
Defective
valve body
Defective high
pressure
sensor
Defective
control
Defective
control
Defective
indoor unit
electronic
expansion
valve
Defective
service
monitor PCB
Defective
valve coil
Defective
valve body
Defective high
pressure
sensor
Defective
indoor unit
liquid pipe
thermistor
Defective
service
monitor PCB
A temperature
difference in
excess of 10˚C
between the
inlet and the
outlet is deemed
to be abnormal.
←
Check to be sure the stop
valve is open.
←
Conduct visual checks for
pipe conditions.
←
Is there any temperature
difference caused before
and after the filter or
branch pipe.
←
Are the coil resistance and
insulation normal?
←
Are the electrical
characteristics normal?
←
Are the coil resistance and
insulation normal?
←
Are the electrical
characteristics normal?
←
Is the connector properly
connected?
Are the thermistor
resistance characteristics
normal?
←
Is the pressure value
checked with the Service
Checker corresponding to
the measurement value of
the pressure sensor?
←
Is the pressure value
checked with the Service
Checker corresponding to
the measurement value of
the pressure sensor?
A