Troubleshooting by Indication on the Remote Controller
156
Troubleshooting
Refer to P.369.
Connector is
connected to outdoor
unit PCB.
NO
YES
YES
Connect the
connector and
turn ON again.
NO
Replace the
thermistor.
Replace the
outdoor unit
PCB.
Confirm which thermistor
is abnormal using outdoor
unit "monitor mode".
Resistance
is normal when
measured after
disconnecting the
thermistor from the
outdoor unit
PCB.
CHECK 11
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
CHECK 11