Troubleshooting by Indication on the Remote Controller
267
Troubleshooting
YES
There are
problems on the
condition of power
supply described
above.
Correct the
problem.
YES
NO
NO
The
insulation
resistance of
compressor is not
more 100k
Ω
.
Replace the
compressor.
YES
NO
The
insulation
resistance of fan
motor is not more
1M
Ω.
Replace the fan
motor.
∗
If the fan
motor is badly
damaged,
replace the
inverter PCB.
CHECK 4
NO
YES
Is the power
transistor
normal?
Replace the
inverter PCB.
A
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Check the condition of the
power supply.
Check if power supply
voltage is 380 to 415V.
Check if there is open
phase or wrong wiring.
Check if power supply
voltage side unbalance
is with in 6V.