Troubleshooting by Indication on the Remote Controller
290
Troubleshooting
YES
YES
NO
In
Confirmation
of error 4, LED
lamp indicates as
follows:?
YES
Check
if indoor
unit PCB or
outdoor unit
PCB has been
replaced. Or check if
indoor-outdoor, outdoor-
outdoor connecting
wires has been
modified.
Press the
RESET button on
the main PCB of
the master
outdoor unit.
Keep pressing
for 5 seconds or
more. (Operation
does not start for
a maximum 12
minutes.)
Replace the
indoor unit PCB.
Correct the
connecting wires.
NO
YES
NO
NO
Do
all the
indoor remote
controllers within the
same refrigerant
circuit display
“
U4
”?
Are
the indoor-
outdoor, outdoor-
outdoor connecting
wires normal?
Check the detailed error
status in the monitor
mode.
(
Go on to P.282.
LED lamp
display
)
A
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.