Troubleshooting by Indication on the Remote Controller
337
Troubleshooting
Has the
setting of
centralized
control group No.
been made with the
indoor unit on
which the “
UE
”
occurred?
Check
the indoor unit
for which “
UE
” is
displayed. Is the
transmission error
(
UE
) caused on
all indoor
units?
YES
NO
Is the
power
supply of the
indoor unit, on which the
“
UE
” occurred,
turned
ON?
NO
YES
Make correct
setting of the
centralized
control group No.
NO
Check outdoor
units to which the
refrigerant
system is
connected.
Make sure there
are no hazardous
situations, and
then turn ON the
power supply.
NO
YES
YES
NO
For VRV
systems, can
the setting of
centralized control
group No. be made in
one and the same
refrigerant
system?
YES
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Can
the setting of
centralized control
group No be
made?
C
A
B