Troubleshooting by Indication on the Remote Controller
253
Remote Controller Display
U0
Applicable Models
VRV-WII and -WIII Series
Method of Error Detection
Detect refrigerant shortage using low pressure or
difference in temperature between the suction pipe and
the heat exchanger.
Error Decision Conditions
In cooling
Low pressure of 0.25 MPa or less continues for 30
minutes
In heating
Suction gas superheated degree of 20°C or more
continues for 60 minutes.
∗
Abnormality is not confirmed and operation is
continued.
Supposed Causes
Refrigerant shortage or clogged refrigerant (wrong
piping)
Defective thermistor
Defective low pressure sensor
Defective main PCB