Troubleshooting by Indication on the Remote Controller
232
Troubleshooting
NO
YES
NO
Connect
transmission
wiring and turn
ON again.
Are the
connectors
between the
outdoor unit main
PCB, fan drive PCB and
inverter PCB
connected
securely?
NO
YES
NO
Check
connection of the
connector.
The micro-
computer monitor
(green) on fan drive
board is
blinking.
YES
Defective
outdoor unit main
PCB or defective
inverter PCB.
The micro-
computer monitor
(green) on the inverter
PCB is blinking.
The
transmission
wiring between
the outdoor unit PCB,
fan drive board and
inverter unit is
disconnected.
YES
Fix the
disconnection
and turn ON
again.
A
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.