Troubleshooting by Indication on the Remote Controller
190
Note:
∗
1. Voltage measurement point
Refer to P.372.
Reset the operation, and
then restart the outdoor
unit.
Are the
characteristics of
the low pressure
sensor
normal?
A
NO
Replace the low
pressure sensor.
YES
Replace the
outdoor unit main
PCB.
Outdoor unit PCB
GND
Micro-computer
A/D input
Low pressure sensor
Red
Black
White
Connector for
low pressure
sensor
CHECK 12
Measure DC voltage here.
4
3
2
1
CHECK 12