Troubleshooting by Indication on the Remote Controller
76
Troubleshooting
NO
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
NO
NO
YES
YES
YES
Connect it and
continue the
operation (It is
possible to have
a cause, such as
instantaneous
blackout).
Confirm the condition of
transmission on indoor
unit PCB using field
setting mode. (
∗
2)
Under
above
field setting mode,
second code No. is
"
01
".
Connect the connector
and turn ON the power
again.
"
C1
"
Reoccurrence
of error.
Is
the
connector
between indoor
unit PCB and fan PCB
accurately
connected? (
∗
1)
Connect the
connector
accurately.
Replace the
indoor unit PCB.
Replace the fan
PCB.