SiUS331604E
Troubleshooting by Error Code
Service Diagnosis
174
Troubleshooting
NO
YES
YES
YES
NO
NO
YES
NO
NO
YES
YES
NO
YES
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the
voltage between L1
and N of power terminal board
X1M within the power supply
voltage ±10%?
Does the fan
motor connector
disconnect?
Are there
any obstacles around
the fan?
Is pin-to-pin
resistance greater than
the threshold value?
Is fuse F6U blown?
Is fuse F6U blown?
Do
the fan blades
spin smoothly by hand after
disconnecting the fan
motor connector?
CHECK 16
Check the fan motor connector.
Calibrate the power voltage.
If L1 and N phases are
disconnected, replace the
power distribution box.
Connect the connector.
Remove the obstacles.
Replace the fan motor.
Replace the fan motor.
Replace the outdoor unit main
PCB (A1P).
Replace the fuse.
Replace the fuse.
CHECK 16
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...