SiUS331604E
Troubleshooting by Error Code
Service Diagnosis
178
4.26 Refrigerant Overcharged
Error Code
F6
Applicable
Models
All outdoor units
Method of Error
Detection
Excessive charging of refrigerant is detected by using the outdoor air temperature, heat exchanger
deicer temperature and liquid pipe temperature during a check operation.
Error Decision
Conditions
During a check operation, the amount of refrigerant will be calculated based on the outdoor
temperature, the heat exchanger deicer temperature, and the liquid pipe temperature. If the
calculated amount exceeds the normal amount by 30%, too much refrigerant has been added.
(Adding only slightly more than the normal amount of refrigerant may also cause
F6
to be
displayed)
Supposed
Causes
Refrigerant overcharge
Disconnection of outdoor air thermistor, heat exchanger deicer thermistor, liquid pipe thermistor
Defective outdoor air thermistor, heat exchanger deicer thermistor, liquid pipe thermistor
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Are the above
thermistor installed on
pipes correctly?
Check the mounting condition of
the outdoor air temperature
thermistor, heat exchanger
deicer thermistor and liquid pipe
thermistor in the piping.
Remove the outdoor air
temperature thermistor, heat
exchanger deicer thermistor and
the liquid pipe thermistor from the
outdoor unit PCB and measure
resistance with a tester.
Rectify the overcharge of the
refrigerant.
YES
NO
NO
Replace the thermistor.
Install the thermistor correctly.
YES
Is the characteristic
of the above
thermistor normal?
CHECK 11
CHECK 11
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...