SiUS331604E
Troubleshooting by Error Code
Service Diagnosis
142
4.5
Indoor Fan Motor Abnormality
4.5.1 Indoor Fan Motor Abnormality (FXDQ, FXHQ Models)
Error Code
A6
Applicable
Models
FXDQ, FXHQ
Method of Error
Detection
This error is detected if there is no revolution detection signal output from the fan motor.
Error Decision
Conditions
When no revolutions can be detected even at the maximum output voltage to the fan
Supposed
Causes
Defective indoor fan motor
Broken wires
Defective contact
Troubleshooting
YES
NO
NO
YES
Check the indoor fan motor and
the wiring circuits of the fan
motor.
Replace the indoor unit main
PCB (A1P).
Properly connect the connectors.
(At this time, check for any
defective connector contact or
broken wires.)
Is the
X4A
connector securely
connected?
Is the
power of
12 VDC
supplied between
the Pins 1 and 3 when
the X4A is disconnected
and the power
supply turns
ON?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...