Field Setting from Remote Controller
SiUS331604E
83
Field Setting
2.3
Setting Contents and Code No. for Indoor Units
: Factory setting
Mode
No.
(
∗
2)
First
Code
No.
Description
Second Code No.
Details
No.
01
02
03
04
10(20)
0
Filter contamination heavy/light
(Setting for display time to clean air
filter)
(Sets display time to clean air filter
to half when there is heavy filter
contamination.)
Ultra
long life
filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
(1)
Long life
filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard
filter
Approx.
200 hrs.
Approx.
100 hrs.
0 (
∗
6)
Filter Sign Setting
Light
Heavy
—
—
1
Long life filter type
Long life filter
Ultra long life filter
—
—
(2)
1 (
∗
6)
Filter cleaning sign time (Light/Heavy)
2,500/1,250
10,000/5,000
—
—
2
Room temperature thermistor in remote
controller
Remote
cont
Suction air
thermistor
Only suction air
thermistor
Only remote
controller
thermistor
—
(3)
2 (
∗
6)
Remote sensor and remote controller
thermistor
Both
Only remote
sensor thermistor
Only remote
controller
thermistor
—
3
Display time to clean air filter calculation (Set
when filter sign is not to be displayed.)
Display
No display
—
—
(4)
6
Remote controller thermostat control during
group control
Remote
controller
thermostat
control is not
permitted
Remote
controller
thermostat
control is
permitted
—
—
(5)
7
Auxiliary electric heater ON/OFF temperature
Refer to page 88.
(6)
11(21)
1
Auxiliary electric heater ON temperature: Ttson
(
∗
8)
Refer to page 88.
2
Auxiliary electric heater OFF temperature:
Ttsoff (
∗
8)
3
Setting the airflow rate when heating
Standard
Slightly
increased
Increased
—
(7)
6
Setting the rate of human detection
High sensitivity
Low sensitivity
Standard
sensitivity
Infrared
presence
sensor
disabled
(8)
7
Airflow adjustment
OFF
Completion of
airflow
adjustment
Start of
airflow
adjustment
—
(9)
8
Compensating the temperature around people
Suction air
temperature only
Priority given on
the suction air
temperature
Standard
Priority given
on the floor
temperature
(10)
9
Compensating the floor temperature
–4°C
(–7.2°F)
–2°C
(–3.6°F)
0°C
(0°F)
+2°C
(+3.6°F)
(11)
12(22)
0
Optional accessories output selection (field
selection of output for adaptor for wiring)
Refer to page 90.
(12)
1
External ON/OFF input (Set when ON/OFF is
to be controlled from outside.)
Refer to page 90.
(13)
2
Thermostat differential changeover
(Set when remote sensor is to be used.)
1°C
(1.8°F)
0.5°C
(0.9°F)(
∗
7)
—
—
(14)
3
Airflow setting when heating thermostat is OFF
LL
Set fan speed
—
—
(15)
4
Automatic mode differential
Refer to page 91.
(16)
5
Power failure automatic reset
Not equipped
Equipped
—
—
(17)
6
Airflow setting when cooling thermostat is OFF
LL
Set fan speed
—
—
(18)
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...