SiUS331604E
Field Setting from Remote Controller
Field Setting
82
2.2
Wireless Remote Controller
To set the field settings, you have to change:
Mode No.
First code No.
Second code No.
Step
Action
1
Press the
INSPECTION/TEST
button for 4 seconds during normal mode to enter
the field setting mode.
2
Press the
MODE
button to select the desired mode No.
3
Press the
UP
button to select the first code No.
4
Press the
DOWN
button to select the second code No.
5
Press the
RESERVE
button to confirm the setting.
6
Press the
INSPECTION/TEST
button to return to the normal mode.
RESERVE
button
INSPECTION/TEST
button
Mode No.
Field setting mode
UP
button
DOWN
button
First code No.
Second code No.
MODE
button