Refrigerant Circuit
SiUS331604E
9
Refrigerant Circuit
1.2
RXTQ48TAVJU
No. in
piping
diagram
Symbol
Name
Function
(1)
M1C
Inverter compressor
Inverter compressor is operated on frequencies between 36Hz and 195Hz by using the
inverter.
(2)
M1F
Inverter fan
Because the system is of an air heat exchange type, the fan is operated at 8-step rotation
speed by using the inverter.
(3)
Y1E
Electronic expansion valve
(Main)
While in heating operation, PI control is applied to keep the outlet superheated degree of
air heat exchanger constant.
(4)
Y1S
Four way valve
Used to switch the operation mode between cooling and heating.
(5)
Y3S
Solenoid valve (Unload circuit) Used for unloading operation of compressor.
(6)
S1NPH High pressure sensor
Used to detect high pressure.
(7)
S1NPL
Low pressure sensor
Used to detect low pressure.
(8)
S1PH
High pressure switch
In order to prevent the increase of high pressure when an error occurs, this switch is
activated at high pressure of 4.0 MPa (580 psi) or more to stop the compressor operation.
(9)
—
Fusible plug
In order to prevent the increase of pressure when abnormal heating is caused by fire or
others, the fusible part of the plug is molten at a temperature of 70 ~ 75°C (158 ~ 167°F) to
release the pressure into the atmosphere.
(10)
—
Pressure regulating valve 1
(Receiver to discharge pipe)
This valve opens at a pressure of 4.0 MPa (580 psi) or more for prevention of pressure
increase, thus resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
(11)
R1T
Thermistor (Outdoor air)
Used to detect outdoor air temperature, correct discharge pipe temperature, and others.
(12)
R2T
Thermistor (Discharge pipe)
Used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.
(13)
R3T
Thermistor (Suction pipe 1)
Used to detect suction pipe temperature, keep the suction superheated degree constant in
heating operation, and others.
(14)
R4T
Thermistor (Heat exchanger
deicer)
Used to detect liquid pipe temperature of air heat exchanger, determine defrost operation,
and others.
(15)
R5T
Thermistor (Suction pipe 2)
Used to the calculation of an internal temperature of compressor etc.
(16)
R7T
Thermistor (Liquid pipe)
Used to detect refrigerant overcharge in check operation, and others.
(17)
FIN
TH
Thermistor (Radiation fin)
• Used for outdoor unit fan speed control.
• Used for inverter radiation fin temperature control.
• Used for pressure difference control.
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...