Troubleshooting by Error Code
SiUS331604E
163
Service Diagnosis
Troubleshooting
Diagnosis procedure 3
Infrared floor sensor error
(Error code
CE-03
)
NO
YES
YES
NO
YES
YES
NO
NO
Turn off the power and then reconnect.
Check infrared floor sensor output; refer to
sensor and address data No. 26.
Is the
connection of the adaptor
PCB connector X9A
normal? (
∗
)
Is the
connection of the
sensor connector
normal?
Displays
"--" by the above
verification
method.
Displays
CE-03
again or "--"
for sensor and address
data.
Replace the sensor.
∗
Check whether A2P connector is well connected or not.
Connect the connector correctly.
Connect the connector correctly.
Normal.
Normal.