Protection Control
SiUS331604E
45
Functions and Control
Heating operation
High pressure drop
Pc > 3.04 MPa (441 psi)
After 10 sec.
Pc > 3.04 MPa (441 psi)
Pc < 2.94 MPa (426 psi)
Pc > 3.64 MPa (528 psi)
Current step maintained
After 60 sec.
High pressure not limited
High pressure limited
Compressor upper limit
frequency: 1-step up from
current compressor frequency
Pc: High pressure sensor detection value
Compressor upper limit
frequency: 1-step down from
current compressor frequency
When occurring 10 times within 60
minutes, high pressure switch is activated
without high pressure standby, thus
outputting the error code
E3
.
Pc < 2.89 MPa (419 psi)
High pressure
standby