6.3.2 With the Optional Infrared Floor Sensor
Whether the thermostat is turned on or off is determined by the difference between the remote controller set
temperature and the detected temperature around people.
•
Normal operation
· Cooling operation
· Heating operation
•
Dry operation
· When Tro
≤
24.5°C (76.1°F)
· When Tro > 24.5°C (76.1°F)
∗
: Description of symbols
∆
T = Detected room temperature – Remote controller set temperature
Tro = Detected room temperature at the start of dry operation
Tr = Determined by the room temperature detected by the thermistor
Control range of temperature around people
When the floor temperature is very low, operation using the temperature around people may cause the suction
air temperature to operate outside of use range.
To avoid the above condition, a limit based on the suction air temperature is set for the use range of the
temperature around people.
•
Heating operation
· When the floor temperature is higher than suction air temperature (R1T), R1T will be treated as the control
target temperature in operation.
· When the temperature around people is 33°C (91.4°F) or higher, R1T will be treated as the control
temperature for operation.
•
Cooling operation
· When the floor temperature is lower than suction air temperature (R1T), R1T will be treated as the control
target temperature for operation.
· When the temperature around people is 15°C (59°F) or lower, R1T will be treated as the control temperature
for operation.
Thermostat OFF
Normal operation
(Thermostat ON)
∆
T
≤
–1.0˚C (–1.8˚F)
∆
T
≥ +
1.0˚C (
+
1.8˚F)
Thermostat OFF
Normal operation
(Thermostat ON)
∆
T
≥ +
1.0˚C (
+
1.8˚F)
∆
T
≤
–1.0˚C (–1.8˚F)
Thermostat OFF
Dry operation
Tr
<
Tro – 1.0˚C (– 1.8˚F)
Tr > Tro + 1.0˚C (+ 1.8˚F)
Thermostat OFF
Dry operation
Tr
<
Tro – 1.5˚C (– 2.7˚F)
Tr > Tro + 0.5˚C (+ 0.9˚F)
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...