Troubleshooting by Error Code
SiUS331604E
195
Service Diagnosis
4.41 Transmission Error between Indoor Units and Outdoor
Units
Error Code
U4
Applicable
Models
All indoor and outdoor units
Method of Error
Detection
Micro-computer checks if transmission between indoor and outdoor units is normal.
Error Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit or
wrong wiring
Outdoor unit power supply is OFF
System address does not match
Defective indoor unit PCB
Defective outdoor main PCB
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
YES
NO
All indoor
unit remote
controllers of the same
refrigerant system
display
U4
.
Is indoor -
outdoor and outdoor -
outdoor unit transmission
wiring normal?
Has
the indoor
or outdoor unit
PCB been replaced,
or has the indoor - outdoor
or outdoor - outdoor unit
transmission wiring
been modified?
NO
YES
Replace the indoor unit PCB
indicated by the error code
U4
.
Fix the indoor-outdoor or
outdoor-outdoor unit
transmission wiring.
NO
YES
Reset the power supply.
Press and hold the RESET
button on the master outdoor
unit PCB for 5 seconds.
∗
The unit will not operate for
up to 12 minutes.
A
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...