Troubleshooting by Error Code
Service Diagnosis
228
Vacuuming and dehydration procedure
Conduct vacuuming and dehydration in the piping system following the procedure for Normal
vacuuming and dehydration described below.
Furthermore, if moisture may get mixed in the piping system, follow the procedure for Special
vacuuming and dehydration described below.
Normal vacuuming and dehydration
(1) Vacuuming and dehydration
• Use a vacuum pump that enables vacuuming up to –100.7 kPa (–14.6 psi).
• Connect manifold gauges to the service ports of liquid pipe and gas pipe and run the vacuum
pump for a period of two or more hours to conduct evacuation to –100.7 kPa (–14.6 psi) or
less.
• If the degree of vacuum does not reach –100.7 kPa (–14.6 psi) or less even though evacuation
is conducted for a period of two hours, moisture will have entered the system or refrigerant
leakage will have been caused. In this case, conduct evacuation for a period of another one
hour.
• If the degree of vacuum does not reach –100.7 kPa (–14.6 psi) or less even though evacuation
is conducted for a period of three hours, conduct the leak tests.
(2) Leaving in vacuum state
• Leave the compressor at the degree of vacuum of –100.7 kPa (–14.6 psi) or less for a period
of one hour or more, and then check to be sure that the vacuum gauge reading does not rise.
(If the reading rises, moisture may have remained in the system or refrigerant leakage may
have been caused.)
(3) Additional refrigerant charge
• Purge air from the manifold gauge connection hoses, and then charge a necessary amount of
refrigerant.
Special vacuuming and dehydration
In case of moisture may get mixed in the piping
∗
(1) Vacuuming and dehydration
• Follow the same procedure as that for Normal vacuuming and dehydration described above.
(2) Vacuum break
• Pressurize with nitrogen gas up to 0.05 MPa (7.3 psi).
(3) Vacuuming and dehydration
• Conduct vacuuming and dehydration for a period of one hour or more. If the degree of vacuum
does not reach –100.7 kPa (–14.6 psi) or less even though evacuation is conducted for a
period of two hours or more, repeat vacuum break - vacuuming and dehydration.
(4) Leaving in vacuum state
• Leave the compressor at the degree of vacuum of –100.7 kPa (–14.6 psi) or less for a period
of one hour or more, and then check to be sure that the vacuum gauge reading does not rise.
(5) Additional refrigerant charge
• Purge air from the manifold gauge connection hoses, and then charge a necessary amount of
refrigerant.
∗
In case of construction during rainy reason, if dew condensation occurs in the piping due to
extended construction period, or rainwater or else may enter the piping during construction
work:
CHECK 8
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...