Outline of Control (Indoor Unit)
SiUS331604E
67
Functions and Control
6.11 Heater Control (FXTQ)
6.11.1 Auxiliary Heater Control
If heating is insufficient in heat pump system alone, an electrical heater is to be used as the
auxiliary heater. The following shows the ON/OFF conditions for the electric heater.
Note:
∗
1. Fixing of the fan H tap.
∗
2. The heater backup prohibiting conditions are prioritized. Even when the heater ON conditions
are met, the heater is turned OFF when the prohibiting conditions are met.
Thermostat OFF/Stop operation
Thermostat step 1
Heat Pump: Fan normal operation
Continues for 5 minutes
Continues for 5 minutes
Continues for 5 minutes
Timer clear
Timer clear
Timer clear
Fan H tap
120 seconds (
∗
2)
Fan H tap
120 seconds (
∗
2)
Thermostat OFF
Condition A
Electrical heater step setting 01
Thermostat step 3 = "ON"
Thermostat step 4 = "ON"
Elimination of Condition A
Elimination of Condition A
Elimination of Condition A
Thermostat step 3 = "OFF"
Thermostat step 4 = "OFF"
Heater 1 ON
Heater 2 ON
Fan H tap (
∗
1)
Heater 1 ON
Heater 2 OFF
Fan H tap (
∗
1)
• Thermostat OFF
• Stop operation
Heater 1 ON
Heater 2 ON
Fan H tap (
∗
1)
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...