Service Diagnosis
188
4.36 Inverter Circuit Capacitor High Voltage
Error Code
P1
Applicable
Models
All outdoor units
Method of Error
Detection
The voltage waveform of the main circuit capacitor of the inverter is used to check for errors.
Error Decision
Conditions
The above-mentioned voltage waveform looks like the waveform of the power supply with a
missing phase
Supposed
Causes
Defective main circuit capacitor
Incorrect main circuit wiring
Defective outdoor unit PCB
Unbalanced voltage between phases
Missing phase
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
NO
YES
YES
Measure voltage between L1 and L2,
L1 and L3, and L2 and L3.
Is three-phase power
voltage within rated voltage
±10%?
Is the
unbalanced phasic voltage
within ±10%?
Calibrate the power voltage.
Calibrate the power voltage.
Replace the outdoor main
PCB (A1P).
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...