Protection Control
Si39-502A
72
Function
4.4
Inverter Protection Control
Inverter current protection control and inverter fin temperature control are performed to prevent
tripping due to a malfunction, or transient inverter overcurrent, and fin temperature increase.
In the case of multi-outdoor-unit system, each INV compressor performs these controls in
the following sequence.
[Inverter overcurrent protection control]
[Inverter fin temperature control]
Nomal operation
Under inverter current
protection control
Invertercurrent >13.5A
Inverter current standby
Inverter current <13.5A
INV upper limit frequency = 210 Hz
INV upper limit frequency: 1-step down
from current compressor frequency
INV upper limit frequency: 1-step up from
current compressor frequency
Invertercurrent >13.5A
Inverter current<13.5A continues
for 20 sec. or more.
Inverter current > 15.0A continues for 260 sec.
&
• When occurring 4 times within 60 min.,
the malfunction code “L8 ” is output.
Tfin>84˚C
Fin temp. standby
Tfin<81˚C
INV upper limit frequency = 210 Hz
Under fin temperature
protection control
INV upper limit frequency: 1-step /
1 min down from current compressor
frequency
INV upper limit frequency: 1-step / 1 min
up from current compressor frequency
Interval
Inverter current<81˚C continues
for 3 min. or more.
&
Tfin>84˚C
Tfin>98˚C
• When occurring 4 times within 60 min.,
the malfunction code “L4” is output.
Nomal operation
Summary of Contents for VRV II RXYQ8MY1K
Page 53: ...Specifications Si39 502A 42 Specifications...
Page 143: ...Field Setting Si39 502A 132 Test Operation...
Page 258: ...Si39 502A Wiring Diagrams for Reference Appendix 247 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 260: ...Si39 502A Wiring Diagrams for Reference Appendix 249 FXKQ25M 32M 40M 63MVE 3D039564A...
Page 264: ...Si39 502A Wiring Diagrams for Reference Appendix 253 FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A...
Page 265: ...Wiring Diagrams for Reference Si39 502A 254 Appendix FXMQ200M 250MVE 3D039621A...
Page 266: ...Si39 502A Wiring Diagrams for Reference Appendix 255 FXHQ32M 63M 100MVE 3D039801C...
Page 267: ...Wiring Diagrams for Reference Si39 502A 256 Appendix FXAQ20M 25M 32M 40M 50M 63MVE 3D034206A...
Page 269: ...Wiring Diagrams for Reference Si39 502A 258 Appendix FXUQ71M 100M 125MV1 3D044973...
Page 270: ...Si39 502A Wiring Diagrams for Reference Appendix 259 FXAQ20MH 25MH 32MH 40MH 50MHV1 3D046348A...
Page 271: ...Wiring Diagrams for Reference Si39 502A 260 Appendix FXLQ20MH 25MH 32MH 40MH 50MHV1 3D046787A...
Page 272: ...Si39 502A Wiring Diagrams for Reference Appendix 261 BEVQ50MVE 3D046579A Notes...
Page 273: ...Wiring Diagrams for Reference Si39 502A 262 Appendix BEVQ71M 100M 125MVE 3D044901A Notes...
Page 285: ...Piping Installation Point Si39 502A 274 Appendix...
Page 293: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 502A 282 Appendix...
Page 307: ...Si39 502A iv Index...