Specifications
Si39-502A
22
Specifications
Slim Ceiling Mounted Duct Type (with Drain Pump)
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 External static pressure is changeable to set by the remote controller this pressure means “High static
pressure - Standard static pressure”.
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
Model
FXDQ40NVE
FXDQ50NVE
FXDQ63NVE
1 Cooling Capacity (19.5°CWB)
RT
1.3
1.6
2.1
kcal/h
4,000
5,000
6,300
Btu/h
16,000
19,800
24,900
kW
4.7
5.8
7.3
2 Cooling Capacity (19.0°CWB)
kW
4.5
5.6
7.1
3 Heating Capacity
RT
1.4
1.8
2.3
kcal/h
4,300
5,400
6,900
Btu/h
17,100
21,500
27,300
kW
5.0
6.3
8.0
Casing Color
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Dimensions: (H×W×D)
mm
200×900×620
200×900×620
200×1100×620
Coil (Cross
Fin Coil)
Rows×Stages×Fin Pitch
mm
3×12×1.5
3×12×1.5
3×12×1.5
Face Area
m²
0.176
0.176
0.227
Fan
Model
—
—
—
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output × Number
of Units
W
62×1
130×1
130×1
Air Flow Rate (H/L)
m³/min
10.5/8.5
12.5/10.0
16.5/13.0
External Static Pressure
Pa
44-15 5
44-15 5
44-15 5
Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polyethylene
Foamed Polyethylene
Foamed Polyethylene
Air Filter
Removal / Washable / Mildew Proof
Removal / Washable / Mildew Proof
Removal / Washable / Mildew Proof
Piping
Connections
Liquid Pipes
mm
φ
6.4 (Flare Connection)
φ
6.4 (Flare Connection)
φ
9.5 (Flare Connection)
Gas Pipes
mm
φ
12.7 (Flare Connection)
φ
12.7 (Flare Connection)
φ
15.9 (Flare Connection)
Drain Pipe
mm
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
Machine Weight (Mass)
kg
27
28
31
6 Sound Level (H/L)
dBA
34/30
35/31
36/32
Safety Devices
Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Standard Accessories
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Drawing No.
C:3D045744
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
RT=kW×0.284
cfm=m³/min×35.3
Summary of Contents for VRV II RXYQ8MY1K
Page 53: ...Specifications Si39 502A 42 Specifications...
Page 143: ...Field Setting Si39 502A 132 Test Operation...
Page 258: ...Si39 502A Wiring Diagrams for Reference Appendix 247 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 260: ...Si39 502A Wiring Diagrams for Reference Appendix 249 FXKQ25M 32M 40M 63MVE 3D039564A...
Page 264: ...Si39 502A Wiring Diagrams for Reference Appendix 253 FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A...
Page 265: ...Wiring Diagrams for Reference Si39 502A 254 Appendix FXMQ200M 250MVE 3D039621A...
Page 266: ...Si39 502A Wiring Diagrams for Reference Appendix 255 FXHQ32M 63M 100MVE 3D039801C...
Page 267: ...Wiring Diagrams for Reference Si39 502A 256 Appendix FXAQ20M 25M 32M 40M 50M 63MVE 3D034206A...
Page 269: ...Wiring Diagrams for Reference Si39 502A 258 Appendix FXUQ71M 100M 125MV1 3D044973...
Page 270: ...Si39 502A Wiring Diagrams for Reference Appendix 259 FXAQ20MH 25MH 32MH 40MH 50MHV1 3D046348A...
Page 271: ...Wiring Diagrams for Reference Si39 502A 260 Appendix FXLQ20MH 25MH 32MH 40MH 50MHV1 3D046787A...
Page 272: ...Si39 502A Wiring Diagrams for Reference Appendix 261 BEVQ50MVE 3D046579A Notes...
Page 273: ...Wiring Diagrams for Reference Si39 502A 262 Appendix BEVQ71M 100M 125MVE 3D044901A Notes...
Page 285: ...Piping Installation Point Si39 502A 274 Appendix...
Page 293: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 502A 282 Appendix...
Page 307: ...Si39 502A iv Index...