Field Setting
Si39-502A
114
Test Operation
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set
1
Cool / Heat
Unified address
8
7
7
7
7
7
8
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
31
8788888
2
Low noise/demand
address
8
7
7
7
7
8
7
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
31
8788888
5
Indoor forced fan H
8
7
7
7
8
7
8
Normal operation
8777778
∗
Indoor forced fan H
8777787
6
Indoor forced
operation
8
7
7
7
8
8
7
Normal operation
8777778
∗
Indoor forced operation
8777787
8
Te setting
8
7
7
8
7
7
7
High
8777877
Normal (factory setting)
8777787
∗
Low
8777778
9
Tc setting
8
7
7
8
7
7
8
High
8777877
Normal (factory setting)
8777787
∗
Low
8777778
10
Defrost changeover
setting
8
7
7
8
7
8
7
Quick defrost
8777877
Normal (factory setting)
8777787
∗
Slow defrost
8777778
11
Sequential operation
setting
8
7
7
8
7
8
8
OFF
8777778
ON
8777787
∗
12
External low noise/
demand setting
8
7
7
8
8
7
7
External low noise/demand:
NO
8777778
∗
External low noise/demand:
YES
8777787
13 Airnet address
8
7
7
8
8
7
8
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
63
8888888
16
Setting of hot water
heater
8
7
8
7
7
7
7
OFF
8777778
∗
ON
8777787
18
High static pressure
setting
8
7
8
7
7
8
7
High static pressure setting:
OFF
8777778
∗
High static pressure setting:
ON
8777787
19
Emergency
operation
(STD compressor is
inhibited to operate.)
8
7
8
7
7
8
8
OFF
8777777
∗
STD 1, 2 operation: Inhibited
8777778
STD 2 operation: Inhibited
8777787
20
Additional refrigerant
charging operation
setting
8
7
8
7
8
7
7
Refrigerant charging: OFF
8777778
∗
Refrigerant charging: ON
8777787
21
Refrigerant recovery /
vacuuming mode
setting
8
7
8
7
8
7
8
Refrigerant recovery /
vacuuming: OFF
8777778
∗
Refrigerant recovery /
vacuuming: ON
8777787
22
Night-time low noise
setting
8
7
8
7
8
8
7
OFF
8777777
∗
Level 1 (outdoor fan with 8 step or lower)
8777778
Level 2 (outdoor fan with 7 step or lower)
8777787
Level 3 (outdoor fan with 6 step or lower)
8777788
Summary of Contents for VRV II RXYQ8MY1K
Page 53: ...Specifications Si39 502A 42 Specifications...
Page 143: ...Field Setting Si39 502A 132 Test Operation...
Page 258: ...Si39 502A Wiring Diagrams for Reference Appendix 247 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 260: ...Si39 502A Wiring Diagrams for Reference Appendix 249 FXKQ25M 32M 40M 63MVE 3D039564A...
Page 264: ...Si39 502A Wiring Diagrams for Reference Appendix 253 FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A...
Page 265: ...Wiring Diagrams for Reference Si39 502A 254 Appendix FXMQ200M 250MVE 3D039621A...
Page 266: ...Si39 502A Wiring Diagrams for Reference Appendix 255 FXHQ32M 63M 100MVE 3D039801C...
Page 267: ...Wiring Diagrams for Reference Si39 502A 256 Appendix FXAQ20M 25M 32M 40M 50M 63MVE 3D034206A...
Page 269: ...Wiring Diagrams for Reference Si39 502A 258 Appendix FXUQ71M 100M 125MV1 3D044973...
Page 270: ...Si39 502A Wiring Diagrams for Reference Appendix 259 FXAQ20MH 25MH 32MH 40MH 50MHV1 3D046348A...
Page 271: ...Wiring Diagrams for Reference Si39 502A 260 Appendix FXLQ20MH 25MH 32MH 40MH 50MHV1 3D046787A...
Page 272: ...Si39 502A Wiring Diagrams for Reference Appendix 261 BEVQ50MVE 3D046579A Notes...
Page 273: ...Wiring Diagrams for Reference Si39 502A 262 Appendix BEVQ71M 100M 125MVE 3D044901A Notes...
Page 285: ...Piping Installation Point Si39 502A 274 Appendix...
Page 293: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 502A 282 Appendix...
Page 307: ...Si39 502A iv Index...